金泉電力的適用范
高壓配(pei)電房配(pei)電設備的(de)操作。各管理處可根(gen)據本(ben)管轄區的(de)實(shi)際情況編(bian)制詳細的(de)操作規(gui)程。
(一)、高壓開關柜的操作
操(cao)作(zuo)程序:
1、 手動(dong)操作方式(shi):運行技工按所需送電(dian)(dian)往每段母線(xian)上,此時(shi)(shi),母聯開關必(bi)須(xu)分閘(zha)。如其中(zhong)一(yi)路(lu)進(jin)(jin)線(xian)失壓或缺(que)電(dian)(dian)時(shi)(shi),即(ji)延(yan)時(shi)(shi)跳(tiao)閘(zha),運行技工可選擇退出其中(zhong)失壓的進(jin)(jin)線(xian)開關,再合閘(zha)母聯開關,送電(dian)(dian)往母線(xian)上恢復供電(dian)(dian)。
2、 自(zi)(zi)動操(cao)作方式:當進線(xian)電(dian)(dian)源正(zheng)(zheng)常時(shi),可選擇自(zi)(zi)動操(cao)作,如有失(shi)壓或缺(que)電(dian)(dian)時(shi),即先(xian)延時(shi)跳閘,再自(zi)(zi)動合閘高壓母聯開(kai)關(guan),恢(hui)(hui)復(fu)供電(dian)(dian);但(dan)當進線(xian)恢(hui)(hui)復(fu)正(zheng)(zheng)常供電(dian)(dian)時(shi),母線(xian)開(kai)關(guan)需由值班(ban)人員選擇手(shou)動操(cao)作,并先(xian)分母聯開(kai)關(guan),再合進線(xian)開(kai)關(guan),恢(hui)(hui)復(fu)電(dian)(dian)源正(zheng)(zheng)常供電(dian)(dian)。
(二)、事故處理:
1、 過流故(gu)(gu)障(zhang)(zhang):若線路發生過流時(包括過流,及速斷),該線路開關小車即自動(dong)跳閘,在儀表屏上故(gu)(gu)障(zhang)(zhang)指示(shi)會亮燈。值班人(ren)員(yuan)必須了解故(gu)(gu)障(zhang)(zhang)原因,將(jiang)故(gu)(gu)障(zhang)(zhang)清除(chu),然(ran)后(hou)手動(dong)復位按(an)鈕。
2、 接(jie)地故(gu)障:指示及處理程(cheng)序與過流故(gu)障相同。
3、 變(bian)壓器溫升故(gu)障:指示(shi)及處理程序與(yu)過流故(gu)障相同。
4、 失壓跳閘(zha)故障(zhang):指(zhi)示及(ji)處理(li)程序與過流故障(zhang)相(xiang)同。